Customization: | Available |
---|---|
Type: | Self-Starting Diesel Generator |
Installation Method: | Fixed |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Technical data of 2000KW MTU diesel generator | |
Genset Model | 2500GF |
Prime Power | 2000KW/2500KVA |
Rated Voltage | 400/230V |
Frequency | 50Hz |
Power Factor | 0.8(lagging) |
The regulating rate of steady voltage | ≤±0.5% |
The regulating rate of instantaneous voltage | ≤-15%/ +20% |
The time of steady voltage | ≤1.5sec |
The waving rate of voltage | ≤1.0% |
The regulating rate of steady frequency | ≤3% |
The regulating rate of instantaneous frequency | ≤±10% |
The time of steady frequency | 3sec |
Dimension (L×W×H) (mm) | 6550*2600*2500 |
Genset weight (kg) | 20500 |
Diesel Engine specification | |
Brand | MTU |
Number of Cylinders | 20 |
Rotating Speed | 1500RPM |
Cycle | Four stroke |
Type | four strokes, Vertical, V- type, water-cooling |
Bore×Stroke(mm) | 170*210 |
Displacement(L) | 95,4 |
Lubricating Capacity(L) | 390 |
Speed Governor | Electrical |
Cooling System | Water-cooled |
Speed Stability (%) | ≤5% |
Fuel Consumption at 100% Load | 192g/kw.h |
Starting Method | DC24V Electrical starting |
Alternator specification | |
Brand | Leroy-Somer |
Number of Phase | 3 |
Connecting Type | Three Phase and Four Lines |
Number of Bearing | 1 |
Grading Protection | IP23 |
Altitude | ≤1000m |
Exciter Type | Brushless (AVR automatic voltage regulating) |
Insulation Class | H degree |